Manufacturing of 2TE Horizontal Multi-Stage Centrifugal Pump System for a Hospital Industrial Boiler Room Application

Smart Turner Pumps Inc builds all units and industry projects to individualized end user specifications with special considerations and requirements honored and adhered to. The above indicated horizontal multi-stage centrifugal pump skid mount system was no exception. With the unit environment being that of a hospital boiler room, there were a host of standards to meet, including TSSA, ASME, EEMAC, IEEE, NEMA and several others, we designed and constructed to the system to exacting requirements.

Our commitment to quality continues at the site through our pump start up commissioning and vibration analysis to ensure proper functionality of the pump for years to come. Designed to be a readymade drop in complete unit, the overall project is a classic example of our breadth of expertise over a huge range of industries and product types that vary from individual pumps to fully functioning systems.

Horizontal Multi-Stage Centrifugal Pump System Highlights

Product Description These 2TE Horizontal Pump System is used in a Boiler Feed Water Application
Capabilities Applied/Processes Castings, Horzontal boring mill, Lathe, Milling Machine
Hydrostatic Testing, Hydostatic Testing to 450 psi / 10 minutes.
Witness Start-up of pumps and to make sure everything is running smoothly.
Overall Pump Dimensions Length: 100"
Width: 61.6"
Height: 25.0"
Suction Inlet: Ø4"
Discharge Outlet: Ø2"
Tightest Tolerances ±.0005
Material Used Pump: Cast Steel ASTM A216 Grade WCB
Impellers: Cast 410 Stainless ASTM A217 Grade CA15
Pump, Shaft: 410 Stainless Steel
Shaft Sleeves: 316 Stainless Steel
Features Pump
154 USGPM
529 feet head
3,500 RPM
Motor Specifications:
75 HP
3,600 RPM
3/60/575 Volt
TEFC Enclosure
365TS Frame
IEEE841 Severe Duty
NEMA Premium Efficiency
ANSI FF Flanged Connections
Pump Flow Data Fluid: Water
Viscosity of .2183 cP
Temperature of 250°F
Estimated Part Weight 2,275 lbs.
Industry for Use Boiler Feed Pump for Hospital Industrial Boiler
Quantity 3
Turn Around Time 12-14 Weeks After Approval of Drawings
Delivery Location London, Ontario
Standards Met Customer supplied specifications
ANSI
B31.1-Power Piping
B16.5-Pipe Flanges,and Flanged FIttings
ASME
Hydraulic Institute Standards (HI)
Canadian Standards Association (CAS)
Electrical and Electronic Manufacturers Association of Canada (EEMAC)
Institution of Electrical and Electronic Engineering (IEEE)
National Electrical Manufacturers Association (NEMA)
Ontario Electrical Safety Code
Occupational Health and Safety Act
Technical Standards & Safety authority (TSSA)
Product Name Manufacturing of 2TE Multi-Stage Boiler Feed Pump